Liberal Arts/Arts & Humanities (LAAH)

 

In collaboration with facility coordinators, the following adjustments have been made to the building: 

  • 160+ VAV motors had incorrect timing sequences corrected.
  • 110+ air filters were identified and placed on a pm schedule (mostly within the VAV boxes).
  • Identified deficient occupancy sensors. Reprogrammed/repaired as needed including firmware updates, Ultrasound and PIR sensitivity adjustments.
  • Closed 10+ HHW bypass valves which significantly lowered consumption during the cooling season.
  • Identified 90+ spaces being over-conditioned due to inaccurate minimum flows.
Commodity Baseline Consumption Actual Consumption Avoided Consumption
Electricity (kWh) 698,997 595,308 $8,178
Chilled Water (mmBtu) 5,555 3,839 $26,054
Heating Hot Water (mmBtu) 1,318 682 $9,812
Total Savings $44,044
*April 2017 - April 2018