Interdisciplinary Life Sciences Building (ILSB)

 

In collaboration with facility coordinators, the following adjustments have been made to the building:

  • Calibrate sensors to modify Air Changes per Hour (ACH) according to AHSRAE Standards.
  • Repaired all Enthalpy wheels, and revised the Enthalpy wheel control sequence to optimize energy performance.
  • Repaired exhaust fan dampers that were causing fans to not reach setpoint and dampers that were found stuck in position.
  • Repaired failed points for all fume hoods. Made mechanical modifications to 21 fume hoods to convert from CAV to VAV controls.
  • Outdoor air control is now based off of classroom CO2 levels rather than hall CO2 levels.
  • Modified Relief Air Flow Levels that were found to be set too high.
  • Corrected synchronization issues by updating firmware on all Siemens field panels.
  • Re-assigned sensors that were found to be crossed for different rooms.
Commodity Baseline Consumption Actual Consumption Avoided Consumption
Electricity (kWh) 7,393,361 7,330,457 $4,897
Chilled Water (mmBtu) 46,616 42,763 $58,507
Heating Hot Water (mmBtu) 13,984 13,403 $8,957
Total Savings $72,361
*February 2017 - February 2018